Module with 2 NTC inputs, 2 ditigal inputs and router
DB2-2NTC-IO-BOO
![]() |
Key features
|
The DB2-2NTC-IO-BOO can read at the same time the temperature with the 2 on board NTC inputs and the 2 digital inputs and send them at regular intervals to one of a Gateway of the Digitron products family.
This device may be confi gured to manage alarm thresholds when exceeding maximum or minimum levels of temperature.
This device can perform data transmissions automatically and immediately (regardless of confi gured sampling rate) in order to signal a status change in one of the two digital inputs.
The device is supplied at 12-24 Vdc/Vac continuously; therefore it can also act as a repeater or a parent device for
battery-powered sensors.
Technical Specs
|
|
General characteristics
|
Chip Ember EM250
Compatible IEEE 802.15.4 Stack EmberZnet 3.5.x (ZigBee PRO) Modbus/RTU Device address settable via internal dip-switch Wall mounting with screws Cable gland: PG9 |
RF characteristics
|
Frequency: 2405 MHz ÷ 2480 MHz
Modulation: DSSS Nominal transmission power: 10mW (10 dBm) Reception sensitivity: -97 dBm External antenna gain: 5,5 dB Coverage outdoor/indoor: 200m/50m |
Supply
|
12/24Vcc/Vca; 100mA; 50/60Hz
|
Thermal sensor input
|
NTC sensor
103AT type (R25 = 10 KOhm; Beta = 3435K) Measurement range: -50°C ÷ +100°C Measurement resolution: 0,1°C Measurement accuracy: ±0,5°C Measures are linearized at tenth of degree |
Digital inputs
|
Electronic type not insulated inputs for clean contact
Short circuit current 0,01mA. Use self-cleaning contacts |
Connections
|
Pull out terminals (3,81 mm pitch)
|
Environment parameters
|
Operating temperature: -10 ÷ +60°C; <80% U.R. not condensing
Storage temperature: -20 ÷ +70°C; <80% U.R. not condensing Degree of protection: IP 55 |
Compliant with 2006/95/EEC,
89/336/EEC, 99/5/EEC directives
Reference Norms
|
ETSI EN 300 328: Radio Compatibility for digitals wide band transmissions
ETSI EN 301 489: Radio Compatibility EN 61000-6-2: Electromagnetic Compatibility - Emissions EN 61000-6-3: Electromagnetic Compatibility - Immunity EN 60950-1: Electric Safety |