Field adjustable, multi-range differential pressure transmitters for air
DPT-R8
DPT-R8 series devices include:
• Multiple measurement units, field selectable via jumper, including: inWC, mmWC, Pa, mbar.
• 8 field selectable measurement ranges, unidirectional or bi-directional, selectable via jumper (see Product Information).
• Proportional output options including: voltage (0–10 V) and current (4–20 mA).
DPT-R8 series devices are commonly used in HVAC/R systems for:
• fan, blower and filter monitoring
• pressure and flow monitoring
• valve and damper control
• pressure monitoring in cleanrooms

Technical specifications
Response Time:
0.8 / 4 s selectable by jumper
Measuring unit:
Selectable by jumper (Pa, kPa, mbar, inchWC, mmWC, psi)
Suitable media:
Air and non-aggressive gases
Measuring element:
Piezoresistive
Max pressure:
400 kPa
Accuracy (from applied pressure):
±1,5 % +1 Pa (including: general
accuracy, temperature drift, linearity, hysteresis,
long term stability and repetition error)
Electrical interface:
• Supply voltage: 24 VAC or VDC ±10 %
• Power consumption: < 1.0 W
Output signal:
0…10 VDC, Load R minimum 1 kΩ or
4…20 mA, maximum load 500 Ω
Materials:
• Housing: ABS
• Cover: PC
• Pressure connections: ABS
• Duct connectors: ABS
• Tubing: PVC
Connections:
• Electrical connections: 4 screw terminals, max 1.5 mm2
• Cable entry: M16
• Pressure connections: Male, d=5,0 mm and 6,3 mm
Weight:
150 g, with accessories 290 g
Dimensions:
90,0 x 71,5 x 36,0 mm
General ambient condition:
Temperature range:
• Operation -10…+50 °C (-5…+50 °C for -AZ model)
• Storage: -20…+70 °C
Ambient humidity: 0 to 95 % rH
Safety:
Protection standard: IP54
Conformance:
Meets the requirements for CE marking:
• EMC Directive 2004/108/EY
• Rohs Directive 2002/95/EY